HPE Virtual Connect SE 100Gb F32 Module for HPE Synergy three frame cabling (redundant)

This cabling example shows a redundant three frame configuration.

Prerequisites
HPE Synergy master and satellite interconnect module cabling (nonredundant)
Item Description Amount
1 HPE Virtual Connect SE 100Gb F32 Module for HPE Synergy

(primary master ICM)

1
2 HPE Virtual Connect SE 100Gb F32 Module for HPE Synergy

(secondary master ICM)

1
3 HPE Synergy 50Gb Interconnect Link Module

(satellite ICM)

4
Procedure
  1. Using interconnect link cables, connect the primary master ICM in frame 1 ICM bay 3 to the satellite ICM in ICM bay 3 of frame 2 and 3.
    Figure 88: Master and satellite interconnect modules for three frames - primary master ICM cablingHPE Synergy master and satellite interconnect module cabling (nonredundant)
  2. Using interconnect link cables, connect the secondary master ICM in frame 2 ICM bay 6 to the two satellite ICMs in ICM bay 6 of frame 1 and 3.
    NOTE:

    Ports L1 and L2 of the secondary master ICM must be connected to ports L1 and L2 of the satellite ICM in the same frame as the primary master ICM.

    Figure 89: Master and satellite interconnect modules for three frames - secondary master ICM cablingHPE Synergy master and satellite interconnect module cabling (nonredundant)

  3. Connect two stacking cables from the primary master HPE Virtual Connect SE 100Gb F32 Module for HPE Synergy to the secondary master HPE Virtual Connect SE 100Gb F32 Module for HPE Synergy.
    1. Connect a stacking cable from port Q7 on the first master ICM to port Q7 on the second master ICM.
    2. Connect a stacking cable from port Q8 on the first master ICM to port Q8 on the second master ICM.
    Figure 90: Master and satellite stacking cablingHPE Synergy master and satellite interconnect module cabling (nonredundant)

  4. Cabling is complete.
    Figure 91: Master and satellite interconnect modules for three frames - all cablesHPE Synergy master and satellite interconnect module cabling (nonredundant)