Space

For easy maintenance, follow these guidelines:

Installation method

Space requirements

Workbench-mounting

  • Width of the aisle: ≥ 0.8 m (2.62 ft)

  • Clearance between the rack and walls or other devices: ≥ 0.8 m (2.62 ft)

Rack-mounting

  • Clearance between the rack and walls or other devices: ≥ 1.0 m (3.28 ft)

  • Equipment room height: ≥ 3 m (9.84 ft)


[IMPORTANT: ]

IMPORTANT:

Follow the rack clearance requirements to make sure the switch does not block the rack doors.


HP recommends that you use a rack with a depth of 1.2 m (3.94 ft) for rack-mounting the switch. For the chassis space requirements and rack clearance requirements, see Table 6, Figure 5, Figure 6, and Figure 7. For more information about switch dimensions, see "Appendix A Chassis views and technical specifications."

Table 6: Rack mounting space requirements

Model

Chassis space requirements

Minimum rack clearance requirements

12508E/12518E AC

  • Height:

    • 12508E: 975 mm (38.39 in)/22 RU

    • 12518E: 1686 mm (66.38 in)/38 RU

  • Width: 442 mm (17.40 in)

  • Depth:

    • 859 mm (33.82 in) on switches installed with cable management brackets

    • 913 mm (35.94 in) on switches installed with expansion cable management brackets

  • Distance between the front rack post and the inner side of the front door:

    • 100 mm (3.94 in) on switches installed with cable management brackets

    • 154 mm (6.06 in) on switches installed with expansion cable management brackets

  • Distance between the front rack post and inner side of the rear door: 769 mm (30.28 in) (Including the space for cabling power cords.)

12508E/12518E DC

  • Height:

    • 12508E: 975 mm (38.39 in)/22 RU

    • 12518E: 1686 mm (66.38 in)/38 RU

  • Width: 442 mm (17.40 in)

  • Depth:

    • 759 mm (29.88 in) on switches installed with cable management brackets

    • 813 mm (32.01 in) on switches installed with expansion cable management brackets

  • Distance between the front rack post and the inner side of the front door:

    • 100 mm (3.94 in) on switches installed with cable management brackets

    • 154 mm (6.06 in) on switches installed with expansion cable management brackets

  • Distance between the front rack post and inner side of the rear door: 709 mm (27.91 in) (Including the space for cabling power cords.)

Figure 4: Depth for the 12508E/12518E AC chassis with cable management brackets

(1) Power cabling rack

(2) Cable management bracket

Figure 5: Depth for the 12508E/12518E DC chassis with cable management brackets

(1) Ejector lever on the switching fabric module

(2) Cable management bracket

Figure 6: Depth for the 12508E/12518E AC chassis with expansion cable management brackets

(1) Power cabling rack

(2) Expansion cable management bracket

Figure 7: Depth for the 12508E/12518E DC chassis with expansion cable management brackets

(1) Ejector lever on the switching fabric module