Grounding the switch


[WARNING: ]

WARNING!

For the safety of operators and equipment, securely ground the switch. Make sure the resistance reading between the switch chassis and the ground is less than 1 ohm.


Most racks are equipped with a grounding strip. You can connect the yellow-green grounding cable of the switch to the grounding strip.


[CAUTION: ]

CAUTION:

Connect the grounding cable to the earthing system in the equipment room. Do not connect it to a fire main or lightning rod.


Use the supplied grounding cable (CAT 6 cable with dual-hole ring terminals).

To connect the grounding cable:

  1. Remove the two grounding screws from the switch chassis.

  2. Use the grounding screws to attach one end of the grounding cable to the chassis.

  3. Connect the other end of the grounding cable to the grounding strip of the rack in the same way.

Figure 23: Connecting the grounding cable for the 12508E

If there is no grounding point on the rack, you can attach the grounding cable to a grounding strip. The installation procedures are similar.